How to Size a Unit Heater for Your Space
To size a unit heater, calculate the building’s heat loss to find the heating load in BTU/hr. Then choose a heater whose heat output, not just its input rating, meets that load. Square footage gets you close, but insulation, air leakage through doors and windows, and how you use the space all change the number. This page is for building owners, facility managers and contractors choosing a gas-fired unit heater for a garage, shop or commercial building. It covers what sets the heating load, what goes wrong when a heater is too big or too small, and five steps to the right size.
Key Takeaways
- Square footage alone does not determine heater size. A unit heater effectively heats a space when it is properly matched to the application’s requirements.
- BTU/hr Input VS. Output: Input BTU/hr is the rate of fuel energy the heater consumes per hour at its rated firing rate. Output BTU/hr is the useful heat the heater actually delivers into the space after combustion and venting losses.
- Insulation and air infiltration change the heating load more than any other factor.
- An oversized heater short cycles; instead of running in longer, steady heating cycles, the equipment spends more time starting and stopping. That can create uneven temperatures throughout the space, increase wear on components, and reduce overall operating efficiency.
- Modine gas-fired unit heaters run up to 400,000 BTU/hr each, so larger spaces may require multiple units.
- A qualified or licensed HVAC professional should always conduct a comprehensive heat-loss calculation prior to buying a heater. Additionally, they must verify the installation requirements and ensure compliance with local and national codes before acquiring a unit heater.
On this Page
- What size unit heater do I need?
- Sizing a Garage Heater Is a Critical Part of the Process
- Heat Loss Calculation
- What Happens If You Oversize a Unit Heater
- What Happens If You Undersize a Unit Heater
- The Variables That Determine Unit Heater Sizing
- How to Size a Unit Heater in Five Steps
- Frequently Asked Questions (FAQs)
What size unit heater do I need?
You need a heater whose output matches your building’s heating load. Three numbers get you there, all measured in BTU/hr (British thermal units per hour). Heat loss is how fast the building loses heat in cold weather. The heating load is the heat you have to replace to hold your target indoor temperature. Heating capacity is how much heat the heater delivers. The right heater’s capacity meets the load.
Sizing a Heater Is a Critical Part of the Process
Once you’ve decided to heat your space, it is essential to select the correct unit size for the space. If your heater is too small, it will take a very long time to reach your desired comfort level, if at all. Buying a unit heater that is too big will cycle on and off frequently, creating drastic temperature swings and increasing wear and tear on your unit heater. Making the wrong selection could end up leaving you uncomfortable and frustrated.
Heat Loss Calculation
A full heat loss calculation by a qualified licensed heating professional should always be done before purchasing a heater.
This calculation will take into account the building’s construction, such as walls, windows, floors, garage doors and the ceiling, as well as the amount of insulation used in the space.
These calculations are always done best by a qualified licensed heating professional. Many times this will be the same individual who purchases, installs and services your heater.
Compare output, not input. Most people compare their heating load to a heater’s input rating. If the space needs 150,000 BTU/hr, they pick a 150,000 BTU/hr unit. But input refers to the amount of fuel the heater burns, and output is the amount of heat it delivers, which depends on its efficiency. At 80% efficiency, a 150,000 BTU/hr input unit puts about 120,000 BTUH into the space. The output is what heats the building, so that’s the number to match to your heating load.
Where to get the number. Modine HVAC helps with product selection, but it doesn’t size jobs. Sizing is done by a qualified, licensed heating professional, and many of them use software to run the calculation. To get the right system for your space, use Modine HVAC’s Where to Buy tool to find a qualified, licensed heating professional near you.
What Happens If You Oversize a Unit Heater
Oversizing is the most common sizing mistake. It’s an old common misconception that a bigger heater is safer. A space that needs a 100,000 BTU/hr heater gets a 150,000 BTU/hr heater instead, on the theory that more heat can’t hurt. It can.
An oversized heater heats the space too fast and shuts off, then starts again when the space cools. That’s known as short cycling. The ANSI Z83.8 standard for gas-fired unit heaters sets a maximum time for a unit to reach its minimum operating temperature, which works out to about 5 minutes for most Modine HVAC units. A heater that shuts off sooner may never get there.
You’ll notice short cycling right away. The space swings from hot to cold, and the unit turns on every few minutes even when it isn’t very cold outside. A longer cycle feels more comfortable and also removes humidity from the air.
Short cycling also shortens the heater’s life:
- The heat exchanger heats and cools quickly, over and over. The metal expands and contracts, which can crack it.
- Moisture condenses inside the heat exchanger when a cycle is too short to burn it off, and it causes rust.
- The ignition control and fan motor switch on and off far more often than they’re designed to, so they wear out sooner.
A leaky or poorly insulated building does need more BTU/hr. That’s a reason to calculate the load correctly, not a reason to guess high.
What Happens If You Undersize a Unit Heater
An undersized heater runs and puts out heat but can’t keep up on the coldest days. The space never reaches its set temperature, and the heater burns fuel without making the building comfortable. That’s a sizing problem, not an equipment fault.
To tell an undersized heater from a failing one, a qualified HVAC technician checks three things:
Gas pressure. Is the right gas pressure reaching the unit?
The burners. Are they lighting and running?
The temperature rise. How much warmer is the air leaving the heater than the air going in? Every unit has a rated temperature rise, often somewhere in a range like 40 to 70 degrees. If the measured rise falls within the unit’s rating, the heater is working.
If all three check out and the building is still cold, the heater is too small. The fix is adding heating capacity, either another unit or another heat source.
The Variables That Determine Unit Heater Sizing
Eight variables set a building’s heating load. The two that move it most are insulation and air infiltration.
| VARIABLE | WHAT IT CHANGES |
| Building dimensions | The floor area and volume of air to heat |
| Ceiling height | How much air volume sits above the floor area |
| Construction and insulation | How fast heat escapes through the walls, roof and floor. One of the two biggest factors. |
| Outdoor design temperature | How cold it gets at the worst conditions the heater has to handle |
| Indoor design temperature | The temperature you hold the space at. Some spaces are kept at 60 degrees, and others are held warmer. |
| Air infiltration | Cold air coming in through leaky doors, windows and overhead doors, which the heater has to warm. One of the two biggest factors. |
| Building use | How the space is used and how often doors are opened |
| Ventilation requirements | Outside air brought in on purpose, which also has to be heated |
Air infiltration is the hardest variable to estimate yourself. Codes publish standard air change rates, but Modine HVAC doesn’t publish infiltration assumptions by building type. A qualified licensed heating professional running the heat loss calculation can apply the right values.
How to Size a Unit Heater in Five Steps
- Gather the building information: Building Dimensions, Ceiling Height, Materials and Construction, Outdoor Design Temperature, Desired Indoor Temperature, Air Infiltration, Ventilation Requirements, and Building Use.
- Calculate heat loss. Connect with a qualified licensed heating professional to run a full heat loss calculation.
- Establish the heating load. Translate the heat loss into the BTU/hr needed to hold the desired indoor temperature on the coldest days.
- Select a heater with a heating capacity that meets the heating load. Compare the load to each heater’s output, not its input. Modine gas-fired unit heaters run up to 400,000 BTU/hr each, so a large building may require several units sized to share the load.
- Verify the heater selected meets the applications needs. Once you know your BTUH range, the right model depends on what matters in the space. Heat throw can push you to a different style of heater. You may need a quieter unit where people work, a more efficient unit to save fuel, or a standard unit to keep upfront costs down. Mounting height and venting requirements can differ across Modine HVAC’s gas-fired unit heater lines. Always refer to the applicable Installation & Service Manual and applicable local and national codes for specific installation requirements.
Ready to narrow it down? Use the Modine Heating Solutions Advisor, or browse Modine HVAC’s gas-fired unit heaters.
Frequently Asked Questions (FAQs)
How many BTU do I need to heat my space?
You need a heater whose output matches your building’s heating load, which comes from a heat loss calculation. For example, a 120,000 BTU/hr load calls for about 150,000 BTU/hr of input from a heater running at 80% efficiency.
Can I size a unit heater by square footage?
Square footage gets you close, but it can’t account for overall heat loss (the amount of heat that naturally escapes from the building through its walls, roof, doors, windows, and air infiltration). Those can change the load more than the floor area does, so use a heat loss calculation for the final size.
What happens if a unit heater is too big?
It short cycles, turning on and off every few minutes, and a cycle under about 5 minutes may not reach operating temperature. The repeated heating, cooling and condensation wear out the heat exchanger faster.